|
| About HMI Excess Flow
Check Valves |
HMI
Excess Flow Check Valves are normally open safety valves for
installation in lines flowing into and out of pressure tanks.
Their main function is to stop the full flow of the tanks
liquid contents automatically should a flow line rupture and
reset automatically when repairs are made. Therefore, they
should be installed in the tank fitting or as near as
possible to the tank.
HMI
Excess Flow Check Valves are reliable, simple, totally
mechanical and very effective. When a line breaks the
increased velocity of flow creates a pressure drop across the
valve which over comes the preset maximum flow setting of the
valve and the valve closes. After the excess flow check valve
is triggered it will remain closed until the flow line is
repaired and the pressure is balanced automatically across
the valve.
HMI
Excess Flow Check Valves can be used in other piping systems
to limit flows to a predetermined maximum flow. The excess
flow check valve will allow flow in either direction but will
only trigger in the specified flow direction.
Each
HMI Excess Flow Check Valve is designed for a particular flow
application and maximum flow rate. It will flow any rate less
than this rate but will close when this rate is exceeded.
Slight weeping will occur when closed, this is normal, it
allows the valve to reset automatically to the normally open
position after repairs are made.
Installation
& Testing:
Excess
flow check valves should be installed in lines flowing into
and out of pressure tanks. Installation should be as near as
possible to the tank. After installation, excess flow check
valves should be periodically inspected to ensure they
function as intended.
A
quick way to demonstrate whether the excess flow valve is
working properly is to increase the flow rate over the rated
capacity of the valve. The valve, if working properly, will
close due to the increased flow velocity. Of course, make
sure this testing method is acceptable for your situation and
that it does not pose a hazard or damage equipment.
Cautions
& Warnings:
Helmco
recommends periodic inspection of any excess flow check
valve. Failure to do so could result in valve failure when it
is needed which could cause damage to equipment, i.e. pumps,
etc. or in some cases cause personal injury or death. HMI
Excess Flow Check Valves are inspected and tested before
shipment to ensure they flow the customer specified maximum
flow rate and close when the maximum flow rate is exceeded.
It is the customers responsibility to install the excess flow
check valve properly and in accordance with certain
regulatory agencies, if any, and to periodically inspect/test
in accordance with the customers preventive maintenance
schedule and keep a record of these inspections. HMI
recommends inspection and testing all excess flow check
valves at intervals not exceeding one year.
The
single most important warning for excess flow valves is:
| Make sure the excess flow valve
closes when the flow rate exceeds the normal expected
flow. |
This can
only be accomplished thru routine maintenance and testing.
This not only checks the condition of the excess flow valve
but will also alert the operator if the proper valve has been
selected and if it has been installed properly.
Reasons
excess flow valves fail:
1.
Upstream pressure too low to produce an excess flow.
2.
Too many restrictions downstream in the piping system ( example:
reduction of pipe size, length of downstream pipe too long,
too many fittings, a partially closed valve downstream.
3.
A flow line downstream has ruptured but the break is not
large enough to cause an excess flow (example:
a split or tear in the flow line).
4.
Foreign material lodges in the valve preventing it from
closing.
5.
Tampering with the excess flow valve by attempting to get
more flow than the valve was designed for.
6.
Prolonged hammering of the excess flow valve, which damages
the valve.
Do
not oversize an excess flow check valve. To do so will cause
the valve to never be subjected to an excess flow because the
valve would be set to trigger at a flow rate higher than you
are capable of flowing. Example:
You are capable of pumping 300 gpm maximum thru a line
without an excess flow check valve. You install an excess
flow check valve set to trigger at 500 gpm. The valve will
never close because it will never be subject to a flow over
500 gpm.
Do
not reduce downstream piping smaller than the rated size of
the excess flow valve. Do not add other restrictions
downstream such as too many valves, fittings, flow meters or
excessive piping. Testing the excess flow valve after
installation will reveal if it is installed properly and is
recommended by HMI.
HMI
offers an in-house re-manufacturing service on HMI Excess
Flow Check Valves should the customers maintenance personnel
determine the excess flow valve is in need of repair or
calibrating. Simply return the valve prepaid to HMI and we
will evaluate the valve and inform you the cost to repair. In
most cases, repairs and calibrating are less than half the
cost of a new excess flow check valve.
All
HMI Series Excess Flow Check Valves are near chatterless due
to our improved design which should greatly extend the
service life of the excess flow valve. However, any excess
flow check valve of this type can be made to hammer. Some
operators have the misconception that the excess flow check
valve is flowing it's maximum capacity when it is hammering.
In fact, the flow is greatly reduced at this point and
prolonged hammering will damage the valve which can lead to
valve failure or damage to equipment and possible injury or
death.
Back
|